Inversion of concrete parameters of gravity dam based on measured temperature and deformation

CHEN Yi, LIN Shuting, SU Bowen, WANG Zhenhong, ZHANG Bu, WANG Juan and ZHANG Kaiheng
  

  1. Huadian Fuxin Zhouning Pumped Storage Co., Ltd.
  • Received:2024-09-18 Online:2025-06-30 Published:2026-01-31

摘要:

在大体积混凝土仿真分析中,各热力学参数对计算结果的影响很大。现有的混凝土热力学参数多为实验室所得数据,而混凝土在经过水化热反应及周围环境因素的影响后,性质难免发生改变,其热力学参数较实验室数据有较大出入,影响有限元仿真计算的准确性。为了得到准确的热力学参数,结合福建周宁抽水蓄能电站下水库大坝实测资料,对混凝土的绝热温升等热力学参数进行反演分析,通过建立三维有限元模型,计算典型坝段的温度和应力场,根据计算结果构建最优解目标函数,从而得出最优热力学参数。研究结果显示,采用反演分析获得的热力学参数结果与实测值对比相对误差较小,表现出了较高的精度。在周宁抽水蓄能电站下水库大坝中,实际绝热温升较设计参数有所增加,混凝土的最高温度比设计参数提高了约3℃,线膨胀系数较设计值减小了0.6,弹性模量则有1.8 GPa左右的提升。本次反演中各参数的变化规律经计算后证明其与实际相贴合,可为类似工程提供参考。

关键词:

Abstract:

In the simulation analysis of mass concrete, thermodynamic parameters exert great influence on the calculation results. Existing thermodynamic parameters of concrete are mostly obtained from laboratory. However, the hydration heat reaction of concrete and the influence of surrounding environmental factors on concrete would inevitably change the performance of concrete, and there is a great gap between actual thermodynamic parameters and laboratory data, which would affect the accuracy of finite element simulation calculations. To obtain accurate thermodynamic parameters, combining with the measured data of the lower reservoir dam of Fujian Zhouning pumped storage power station, inversion analysis of the thermodynamic parameters is carried out, such as adiabatic temperature rise of concrete, surface heat dissipation coefficient, coefficient of linear expansion and elastic modulus, etc. Moreover, a three-dimensional finite element model is set up to calculate the temperature and stress field of a typical dam section. Then, the optimal solution objective function is constructed based on the calculation results, so as to obtain the optimal thermodynamic parameters. The results show that the thermodynamic parameters obtained by inverse analysis have a small relative error compared with the measured values, and show high accuracy. As to the lower reservior dam of Zhouning pumped storage power station, the actual adiabatic temperature rise is greater than the design parameters, the maximum temperature of concrete is 3°C higher than the design parameters, the coefficient of linear expansion has decreased by 0.6 compared with the design value, and the modulus of elasticity has increased by about 1.8 GPa. The rule of change of each parameter in this inversion is proved to be consistent with the actual situation, which can be used as a reference for similar projects.

Key words: